Technical
-> K-Factor Transformers
Most transformers are used to supply power to loads that
draw current with a sinusoidal waveform (blue). However some
types of load particularly, smoothed DC power supplies, draw
the current as a pulse during a small part of the mains cycle
(red).

This pulse can, when analysed, be shown to consist of a series
of sine waves of varying amplitude which occur at integer
multiples of the source (or fundamental) frequency. These
integer multiples of the fundamental frequency are known as
harmonics.
The French mathematician Fourier developed a theorem in which
these current pulses ‘I’ can be described by the
following equation.
Where ‘ω’ relates to the fundamental frequency
of the system. ‘n’ is an integer series
making ‘nω’ the harmonics and ‘An
’ is the amplitude of nth harmonic
component in the series
Large power transformers are prone to a loss mechanism associated
with the coils known as “Eddy Current Losses”.
Eddy current losses are expressed as a percentage of the transformers
normal resistive coil losses (I²R) as determined by Ohms
law. They are a phenomena that increases in severity as the
frequency of the current increases hence the presence of harmonic
content in the current waveform will have the effect of increasing
the self heating of a transformer.
That is to say a transformer of a specific size operating
with an RMS current of 100A sinusoidal at the fundamental
frequency would when loaded with a 100A RMS current in the
form of a pulse, overheat due to the harmonic effects of the
eddy current losses.
The ‘K-Factor’ is a number calculated from the
harmonic spectrum of the current in a load waveform such that,
regardless of the actual spectrum, loads that require the
same K Factor have the same heating effect on the transformer.
In this way any load can be specified by its K-Factor and
transformer compensation for K-Factor becomes standardised.
Typical K-Factors that are specified are 4, 10, 13 and 20.
The higher the number the worse the harmonic load and the
greater the compensation required.
The effective rating KVAEFF of a transformer required
to supply power to a K-Factor load is given by the equation

Where
| KVAACT |
is the power required by the system |
| K |
is the K factor of the load |
% |
is the eddy current loss factor expressed as a decimal
(5% = 0.05) |
It should be noted that some effort can be made in the design
of the transformer to reduce the required size increase by
reducing the eddy current losses ‘%’
K-Factor Calculation
The K-Factor is calculated from the harmonic spectrum of
the load current by the following equation

Where the value In is the amplitude of
the nth harmonic current normalized such
that

Where IRMS is the total RMS load current
Neutral Bars
One particular feature of K-Factor transformers is they are
subject to large currents flowing within the neutral line.
With a normal transformer supplying a balanced system of purely
sinusoidal loads at the fundamental frequency the total current
flowing in the neutral line is given by
As with a balanced load I1 = I2 = I3
and by definition

i.e the currents cancel out so no current flows in the neutral
line. In practice there are usually some small differences
between the currents in each phase such that a small current
amounting to a few percent of the rated load current flows.
When harmonics are present however the neutral current is
given by

Here the 3rd, 9th etc harmonics do not cancel out but reinforce
as
Hence the neutral current will be given by

Typically K-Factor transformers are fitted with neutral bars
that are rated for double the normal rated load current of
the transformer
More
product information
|