-> Three Phase to Single Phase Transformer Options
 |
 |
 |
 |
Three Phase to Single Phase Transformer Options |
|
 |
 |
 |
 |
It should be noted that it is impossible
to create a perfect current balance on a 3 phase supply when
feeding a single phase load. Consequently there
are several different methods of producing a single phase
output each of which may be suitable for different circumstances.
Single Phase Transformer
By far the simplest method of obtaining a single phase output
from a 3 phase supply is to place a single phase transformer
across two phases of a 3 phase supply. The effect of this
system is to pull the full rated current in two of the supply
lines and zero current in the third line. This is probably
acceptable up to a rating of about 5KVA on a 400V system (13Amps
/ 13Amps / 0Amps). Above this level an alternative method
may be required to achieve a better balance of currents flowing
in each of the three phases.
Open Delta Transformers
Above 5KVA the most common type of transformer used to supply
a single phase system from a 3 phase supply is the Open Delta
Transformer. This is a transformer built on the two outer
legs of a three phase transformer core. The primary coils
are connected as per a standard 3 phase delta input but with
the “B” coil missing and the secondary coils are
connected as a standard 3 phase star output, again with the
“B” coil missing.
The primary then draws the same current in two of the lines
and the third line carries twice this current. Compared to
the 5KVA single phase system mentioned above the currents
will be 7.5Amps / 15Amps / 7.5Amps
The KVA rating of the transformer is equivalent to the KVA
rating of the load

More
product information
Scott T Transformers
This is another popular method of generating a single phase
supply from a three phase supply this time using two single
phase transformers, The “Main Transformer” and
the “Teaser Transformer” The main transformer
is connected to 2 of the 3 supply lines of the 3 phase system.
The teaser transformer primary is connected between a center
tap on the primary of the main transformer and the third supply
line. Typical currents in the three lines for the 5KVA load
at 400V are 7.5Amps / 10.6Amps / 14.5Amps.
Scott T transformers can be used to supply two separate single
phase loads or the output of the transformers can be joined
to supply one single phase load
The main transformer rating is equivalent to 90% of the load
rating and the teaser transformer about 70% giving a total
of 160% of the load rating

Le-Blanc Transformers
The final 3 phase to single phase converter transformer is
the Le-Blanc transformer. The 5KVA 400V will have line currents
of 3.9Amps / 10.6Amps / 14.5Amps
The transformer rating is equivalent to 120% of the load
rating
|