Type 2 (110V Site Safety System)
This is the 110V CTE or 55-0-55V system. In this system
the 110V output coil has a centre tap in addition to
the two leads at the ends of the coil. The centre tap
is electrically wired directly to the system earth.
With this system a lead must not be connected to one
of the ends of the secondary coil to define the neutral
as this will create a short circuit within the winding.
This type of system is used for power tool operation
throughout Europe. The environment in which these items
are used is generally considered to be hazardous with
the potential for damage to the equipment that could
expose live internal wiring. The centre tap of the system
being earthed limits the magnitude of an electrical
shock under such circumstances to 55V instead of the
full system voltage of 110V
|