Products -> Single
Phase Transformers -> CCM Panel Transformers
A
range of standard transformers with commonly specified
output voltages and multiple input options permitting
use on a full range of European supplies.
- Multi-tapped primary
- Centre tapped secondary
- Insulation between windings
- Short duration surge load capacity
- 50/60Hz operation
- Varnish impregnated windings
- Touch proof terminals
| Power Capability : |
50VA to 1000VA |
| Primary taps : |
+15V / 0V / -15V / 230V / 400V |
| Insulation Class : |
B |
| Isolation Class : |
1 |
| Ambient : |
40°C |
| Pri-Sec Insulation : |
4.5kV |
| Supply Tolerance : |
+6%, -10% |
| Earth Tab : |
Faston 6.3x0.8mm |
The following combinations of rating
and output voltage are available.
Output Voltages
|
Ratings |
50VA |
100VA |
150VA |
200VA |
300VA |
400VA |
500VA |
1kVA |
| 24V (12V-0-12V) |
• |
• |
• |
• |
• |
• |
• |
|
| 48V (24V-0-24V) |
• |
• |
• |
• |
• |
|
• |
|
| 110V (55V-0-55V) |
• |
• |
• |
• |
• |
|
• |
• |
| 230V (0-230V) |
• |
• |
• |
• |
• |
|
• |
• |
Model Designation : CM [rating]
/ [output voltage], e.g. CM500/24
| Options for open style : |
Fuses |
These transformers can also be supplied
in enclosures, with ratings from IP22 to IP55

Rating
|
Click for
Drawing |
Width
(mm) |
Depth
(mm) |
Height
(mm) |
Fixing
Footprint
(WxD mm)
|
Fixing
Hole
Accepts |
Weight |
IP22
Enclosures
|
Click for
Drawing
|
pdf |
dwg |
pdf |
dwg |
50VA |
|
|
76 |
76 |
85 |
62x51 |
M4 |
1.2kg |
WM1* |
|
|
100VA |
|
|
84 |
88 |
92 |
64x61 |
M4 |
1.9kg |
WM1* |
|
|
150VA |
|
|
96 |
92 |
112 |
84x70 |
M5 |
2.7kg |
WM1* |
|
|
200VA |
|
|
96 |
104 |
112 |
84x85 |
M5 |
3.5kg |
WM1* |
|
|
300VA |
|
|
120 |
88 |
120 |
90x68 |
M5 |
4.1kg |
WM2* |
|
|
400VA |
|
|
120 |
102 |
120 |
90x78 |
M5 |
5.1kg |
WM2* |
|
|
500VA |
|
|
120 |
112 |
120 |
90x88 |
M5 |
5.9kg |
WM2* |
|
|
1kVA |
|
|
150 |
150 |
142 |
122x134 |
M6 |
13.0kg |
WM3* |
|
|
* The inclusion of some optional components
may result in a size increase of the indicated enclosure
type
Primary Connection
Instructions |
Supply Voltage |
Connection 1 |
Connection 2 |
220V
|
-15 |
230 |
230V
|
0 |
240V |
+15 |
380V
|
-15 |
400 |
400V
|
0 |
415V |
+15 |
***The CCM range of transformers
replaced our CRT range of transformers. CRT type transformers
may be ordered as spares however they are subject to
lead times associated with built to order transformers
rather than being available ex-works.**
|